Substations
In layman's terms, a substation is a place that changes voltage and distributes electrical energy. To transmit electricity generated by a power plant to distant locations, the voltage must be increased to high voltage. Then, near the user's location, the voltage is reduced as needed and distributed to different users. This process of voltage adjustment and energy distribution is accomplished by substations. Substations are large, have many pieces of equipment, and are relatively dangerous. They typically supply power to users in a specific area, and the low-voltage level of the output voltage is usually above 10kV.
Transformer room, power distribution room
Also known as a substation or distribution room. Simply put: it's a building, or a designated area within a building, where transformers, distribution cabinets, and incoming/outgoing line cabinets are housed. Larger substations typically have more transformers and distribution cabinets. Transformer rooms and distribution rooms can be separate or combined. Transformer rooms and distribution rooms are less hazardous than substations and can be located within or adjacent to buildings for internal use. Their low-voltage output is typically 220V/380V, directly supplying power to electrical appliances.

Prefabricated substations , also known as box-type substations, are devices that organically combine the functions of transformer voltage reduction and low-voltage power distribution. They are moisture-proof, rust-proof, dust-proof, rodent-proof, fire-proof, theft-proof, heat-insulated, fully enclosed, and movable steel structure boxes, making them particularly suitable for urban power grid construction and renovation. They represent a new type of substation that has emerged after traditional civil engineering substations. Generally, they transform high voltage to low voltage, for example, transforming a 10kV line into a 380V working voltage using a transformer. They are mainly used in urban residential areas and streets, where prefabricated substations are needed when voltage increases are required during peak electricity demand periods.
The Building Code contains several provisions regarding substations and power distribution rooms, mainly as follows:
3.2.6 The fire resistance rating of oil-immersed transformer rooms and high-voltage power distribution equipment rooms shall not be lower than Class II .
3.3.8 Substations and distribution stations shall not be located inside or adjacent to Class A or B factory buildings, nor shall they be located in hazardous areas with explosive gases or dust. For 10kV and below substations and distribution stations dedicated to Class A or B factory buildings, when separated by firewalls without doors, windows, or openings, one side may be adjacent, and they shall comply with the provisions of current national standards such as GB 50058 "Code for Design of Electrical Installations in Explosive Atmospheres". If a Class B factory building's distribution station absolutely requires windows in the firewall, Class A fire-resistant windows shall be used.
3.4.11 Outdoor substations and distribution stations with power system voltage of 35kV to 500kV and each transformer capacity of not less than 10MV·A, as well as outdoor step-down substations of industrial enterprises with a total transformer oil volume of more than 5t, shall maintain a fire separation distance from other buildings that is not less than the provisions of Articles 3.4.1 and 3.5.1 of this code.
5.2.3 The fire separation distance between civil buildings and prefabricated substations of 10kV and below shall not be less than 3m.
5.4.12-5 Fire-resistant partitions with a fire resistance rating of not less than 2.00h shall be installed between transformer rooms and between transformer rooms and power distribution rooms .
6.2.7 Fire control rooms, fire extinguishing equipment rooms, fire pump rooms, ventilation and air conditioning machine rooms, power distribution rooms, etc., attached to buildings shall be separated from other parts by fire-resistant walls with a fire resistance rating of not less than 2.00h and floors with a fire resistance rating of not less than 1.50h .
Doors opening into the building from ventilation, air conditioning equipment rooms and power distribution rooms should be Class A fire doors , while doors opening into the building from fire control rooms and other equipment rooms should be Class B fire doors.
8.3.9-1 Automatic fire extinguishing systems should be installed in power distribution rooms and uninterruptible power supply ( UPS) rooms, and gas fire extinguishing systems are preferred.
10.3.3 Fire control rooms, fire pump rooms, standby generator rooms, power distribution rooms, smoke extraction rooms, and fire equipment rooms that need to continue to operate normally in the event of a fire shall be equipped with standby lighting, and the minimum illuminance of their working surfaces shall not be lower than the illuminance of normal lighting.